AMERICAN POWER CONVERSION RACK PDU 2G, SWITCHED, ZEROU RACK PDU 2G, SWITCHED, ZEROU
Manufacturer : AMERICAN POWER CONVERSION UPC : 731304277163
Learn more about the APC AP8961
Model
Brand
APC
Model
AP8961
Details
Type
Switched
Rack Size
0U
Certifications
cUL Listed,FCC Part 15 Class A,ICES-003,UL Listed,VCCI Class A
ROHS
Yes
Input
Input Voltage
208V 3PH
Input Frequency
50/60 Hz
Regulatory Derated Input Current
16A
Input Connector(s)
NEMA L21-20P
Cord Length
6 ft
Output
Output Voltage
208V
Output Connector(s)
(21) IEC 320 C13, (3) IEC 320 C19
Environmental
Operating Environment
-5 - 45 ºC
Operating Relative Humidity
5 - 95%
Operating Elevation
0 - 3000 m
Storage Temperature
-25 - 65 ºC
Storage Relative Humidity
0 - 95%
Storage Elevation
0 - 15000 m
Feature
Features
Network Management:
Full-featured network management interfaces that provide standards-based management via Web, SNMP, and Telnet. Allows users to access, configure, and manage units from remote locations to save valuable time. Associated with this feature is the ability to quickly and easily upgrade the firmware via network download to installed units for future product enhancements.
Remote Individual Outlet Control:
Remotely manage outlets so users can turn outlets off that are not in use (prevent overloads) or recycle power to locked-up equipment (minimize costly downtime and avoid travel time to equipment).
Alarm Thresholds:
Define alarm thresholds in order to avoid overloaded circuits. Network and visual alarms inform the user of possible problems. (Note: Only available on units with the current monitoring capabilities. Please see SKU specifications for availability)
Local Current Monitoring Display:
The aggregate current draw per power distribution unit is displayed on the unit via a digital display. The local digital display helps installers avoid overloaded circuits by providing a visible warning when the current draw is close to the maximum amperage draw of the strip. (Available on designated SKUs only)
Power Delays:
Allows users to configure the sequence in which power is turned on or off for each outlet. This helps avoid in-rushes at start-up, which can cause overloaded circuits and dropped loads. Sequencing also allows users to predetermine which piece of equipment is turned on first so other equipment dependant on that unit will function properly.
Load indicator LED:
Indicates overload and warning conditions based on the user-defined alarm thresholds. Alerts users of potential overloaded circuits.
Dimensions & Weight
Dimensions
70.51" x 2.2" x 1.81"
Weight
15.23 lbs.
Additional Information
Date First Available
February 03, 2023