Next page Line Voltage120/240 Split Phase, 50/60 HzSurge Spike Capacity140,000 AmpsAlarm methodBeeps and Red Service Light FlashesUL 1449 3rd Ed VPRL-N: 600 V, L-G: 600 V, N-G: 600 V, L-L: 900 VRated Voltage (MCOV)150V L-N, L-G, and N-G; 300V L-LResponse Time<1 nanosecondEnclosureIndoor and Outdoor RatedInstallation TypeChase NippleRecommended breaker size20 A Featuring a durable commercial-grade casing, it is suitable for both indoor and outdoor installation.
Features protection status LED, audible alarm, as well as a red service LED.
Compatible with any brand of load center and breaker, designed for surge protection in standard residential split-phase 120/240V, 60Hz system voltage.
Provides a surge current capacity of 140,000 amps per phase.
Know you're protected with Surge Protective Device's 3-stage notification system. When replacement is needed:
Audible Alarm: Beeps
Green LED(s): Extinguish
Red Service Light: Flashes
Ground Reference Monitoring (GRM) by Surge Protective Device. When notifying you a rare safety hazard exists due to a compromised electrical system neutral to ground bond:
Audible Alarm: Beeps
Green LED(s): Remain Lit
Red Service Light: Flashes
Use the nearest breaker to the SPD. Position the SPD close to its intended breaker.
Keep leads short and avoid sharp bends.
Rotate the SPD for optimal LED visibility.
For outdoor installation, ensure weather sealing at the nipple (using gaskets or sealing conduit).
Never Hi-Pot test Any SPD. (will prematurely fail SPD).
HomeSurge is a Type 2 SPD. It is suitable for use downstream of the service disconnect.Pre-Plan your installation. You need to accomplish the following:
Meet all National and Local codes (NEC Article 285 andUL 1449 address SPDs).
Confirm System voltage to SPD voltage (120V SPD will fail instantly on 240V, 277V, etc.).
Mount SPD as close to panel or equipment as possible to keep leads short. (long leads hurt performance).
Ensure leads are as short and straight as possible, including neutral and ground. Use a breaker position that is close to the SPD and the panels neutral and ground.
Make sure system is grounded per NEC and clear of faults before energizing SPD. (inadvertent system problem may fail SPD).
Surge Protector Commercial-Grade Casing Features clear status indicators High Compatibility High Current Capacity Installation Instructions: