Specifications: Output
Output Power Capacity: 10 kWatts / 10 kVA
Max Configurable Power: 10 kWatts / 10 kVA
Nominal Output Voltage: 208 V,208 V 3PH
Efficiency at Full Load: 92.00%
Output Voltage Distortion: Less than 5% at full load
Output Frequency (sync to mains): 57 - 63Hz for 60Hz nominal
Crest Factor: Unlimited
Waveform Type: Sine wave
Output Connections: (1) Hard Wire 5-wire (3PH + N + G)
Input
Nominal Input Voltage: 208 V,208 V 3PH
Input Frequency: 60Hz +/- 3Hz
Input Connections: Hard Wire 5-wire (3PH + N + G)
Input voltage range for main operations: 177 - 239 (208 V) V
Communications & Management
Interface Port(s): RJ-45 10 Base-T ethernet for web / SNMP / Telnet management, SmartSlot
Audible Alarm: Alarm when on battery / distinctive low battery alarm / configurable delays
Approvals: cUL Listed, FCC Part 15 Class A, ISO 140...
Specifications: OUTPUT
Overload protection: 50A DC output fuse
INPUT
Input cord length: 36.00", 8 AWG, 3 conductor
BATTERY
Expandable battery runtime: Includes a second input/output connector to daisy-chain multiple battery packs
DC system voltage: 192V DC
Connects to UPS via: Detachable cable with UPS specific DC connector (90 cm length, 8 gauge)
Specifications: General Battery:
An RBC is a Replacement Battery Cartridge for an Uninterruptible Power Supply (UPS). A UPS is a battery backup power source. 12 volt Batteries.
2 maintenance-free sealed lead-acid batteries (12V 7ah).
Maintenance Free Sealed Lead Acid leak proof batteries.
RBC32 Battery Assembly Technical:
Operating Environment: 0 - 40 deg. C.
Storage Temperature: -15 - 45 deg. C.
Meets or exceeds the original UPS manufacturer's specifications.