Feature 4KW/peak 12KW Low Frequency Pure Sine Wave Inverter with Charger+UPS+USB port, DC48v AC110v 60Hz+AC LCD display, A machine can meet all your needs Inverter AC output Data
Model No.: PSW4000-48-110-AC LCD Continuous Rated output power: 4000W
Peak Surge power: 12000W (keep several seconds)
Output Waveform: Pure sine wave
AC output voltage: 115v±5%
Nominal Inverter Efficiency: >88% (peak) Low and
High voltage trip: 90v±4% & 140v±4%
Low & High voltage re-engage: 100v±4% &135v±4%
Power factor: 0.9 - 1.0
AC output frequency: 60Hz ± 0.3H z Low and
High frequency trip: 57Hz & 65Hz
Output voltage regulation: +/-10%
RMS Short circuit protection: YES, fault after 7 seconds Inverter DC input
Data: Normal
input voltage: 48v
Min start voltage: 40v
Low voltage alarm: 42v
Low voltage trip: 40v
High voltage alarm: 64v
Power save model: YES, when output power less than 20w AC battery charge
Data: AC
input voltage range: 95-127v
Max AC input voltage: 150v DC
Output voltage: depend on battery type
AC charge input amps: 30a, up to the inverter's rated power, max 60a
DC input max amps: 140a Battery initial voltage for starting up: 0- 62.8 v
Over charge protection shutdown: 62.8 v
Bypass and protection: AC
input waveform: pure sine wave
Max AC input voltage: 150v
AC input voltage range: 94-134v
AC input frequency: 60Hz
AC input voltage frequency range: 58-60± 0.3H z
Overload protection: Fuse trip
Short circuit protection: Fuse trip
Bypass current: 30a
Max bypass current: 35a
Bypass over current: YES, 35a
Packing Data weight: 22kg
Size: 30.5 x 21.5 x 33.5 cm
Display of product: LED light+LCD display
Accessories: a pair of cable (suit the inverter) +user manual
Operation A: Inverter Operation 1. input and output terminals, please use the red wire of battery connect the input terminal "+" (red) of inverter, the black wire to connect the input terminal "-" (black) of inverter, and the inverter is 12v, so if your battery is 12v, please hook 4pcs battery in series, then check whether there is short-circuited or not. 2. this is 48v inverter, the rated voltage is 52v. turn on the switch to "on", then the inverter begin to work, the green light will on. 3. shutdown the inverter, please press the switch to "off". 4. the invertr has power save function, you can press the switch to power save, then the inverter will go into sleeping model when the loading is less 20w, and it will scan the loading every 3 seconds, once inverter found there is a loading which over 20w, then the inverter will quit sleeping model.