5/5.8 kW Single-Phase 208 / 240 V Basic 0U 63.75 in. Vertical Rackmount Power Distribution Unit (PDU)
NEMA L6-30P input with 10 ft. (3 m) power cord
38 total outlets - 32 C13 and 6 C19
Switchless design prevents accidental shutdown
+
+
Overview
Specs
Reviews (1)
Learn more about the Tripp Lite PDUV30HV
Model
Brand
Tripp Lite
Model
PDUV30HV
Details
Type
Basic
Rack Size
0U
Style
Vertical
Certifications
Tested to UL60950-1 (USA, Canada), NOM (Mexico)
Input
Input Voltage
200; 208; 240V
Maximum Input Current
30A
Input Connector(s)
NEMA L6-30P
Cord Length
10 ft
Output
Output Voltage
200; 208; 240V
Output Frequency
50/60Hz
Output Connector(s)
6 x C19, 32 x C13
Overload Protection
Outlets are arranged in two separately breakered load banks. The top 15A breaker covers outlets on the upper half, the bottom 15A breaker covers outlets on the lower half of the PDU. Each breakered bank covers 16 x C13 and 3 x C19 outlets.
Feature
Features
208 / 240V 30A Basic Power Distribution Unit (PDU) in 63.75" 0U vertical form factor
30A maximum capacity (Agency derated to 24A)
Attached L6-30P input plug with 10.0 Feet line cord
38 total output receptacles (6 x C19, 32 x C13)
Outlets are arranged in two separately breakered 15A load banks (each with 3 x C19 and 16 x C13 outlets)
Circuit breaker offers protection from overloads and short circuit fault conditions
Sleeved circuit breaker assembly prevents accidental shutoff and requires no tools to reset if tripped
Switch-free unfiltered electrical pass-through reliably distributes UPS or generator power to critical networking equipment
Tooless installation supports fast installation in button-mount compatible equipment racks
Included nut and bolt mounting brackets support installation in non button-mount compatible racks or other flat surfaces, such as under-counter and wallmount