Front Panel LEDs: 16 power availability LEDs confirm power off/on status for each built-in outlet. Two additional LEDs with toggle button identify which bank the visual current meter is reporting (bank 1, bank 2 or bank 1&2 combined)
Certifications: Tested to UL 60950-1 (USA, Canada), Class A (Emissions), NOM (Mexico), RoHS compliant
Front Panel LEDs: Primary and Secondary input connection. Digital current meter display shows the amount of power consumption in amps for entire PDU output.
Certifications: Tested to UL 60950 (USA, Canada), Class A (Emissions), NOM (Mexico), RoHS Complaint
Front Panel LEDs: 8 LEDs display power on-off status for each C13 output receptacle, plus 2 additional LEDs to indicate input power status for primary and secondary inputs
Certifications: Tested to UL 60950 (USA, Canada), CE (Europe), Class A (Emissions), NOM (Mexico)
Front Panel LEDs: 8 LEDs display power on-off status for each C13 output receptacle, plus 2 additional LEDs to indicate input power status for primary and secondary inputs
Certifications: Tested to UL 60950-1 (USA, Canada), CE (EU), NOM (Mexico), GOST (Russia), EN55032:2015 and EN62040-2:2006, FCC Class A (Emissions), TAA Compliant
Features: 230V 32A metered Power Distribution Unit (PDU) in 2U horizontal rackmount form factor
32A maximum capacity
Attached Blue IEC-309 32A input plug with 12 ft. / 3.6m line cord
18 total output receptacles (16 C13, 2 C19)
Outlets are arranged in two separately breakered and metered 16A load banks (each with 8 C13 and 1 C19 outlet)
Current meters offer the ability to visually monitor power consumption levels to prevent mains, generator, UPS or PDU overloads and to ensure proper load balance in complex redundant power applications
Pair of easy to read, two-character LED displays offer continuous PDU current monitoring data in one-amp increments for each metered load bank
Circuit breakers offer protection from overloads a...
Certifications: Tested to UL60950-1: 2007 R10.14 (USA), CAN/CSA-C22.2 NO. 60950-1-07+A1: 2011+A2: 2014 (Canada), FCC CLASS A PART 15 (Emissions), NOM (Mexico), RoHS compliant, TAA Compliant
Certifications: Tested to UL60950-1:2007 (USA), CAN/CSA-C22.2 NO. 60950-1: 2005 (Canada), CE (International), FCC Class A (Emissions), NOM (Mexico), RoHS compliant, TAA compliant
Front Panel LEDs: 19 LEDs display power on/off status for each outlet, plus 2 LEDs for power status on Primary and Secondary input connection and three additional LEDs to label the displayed numeric value as Amps, kW or Voltage
Certifications: Tested to UL 60950-1 (USA, Canada), Class A (Emissions), NOM (Mexico), RoHS Complaint, TAA Compliant
Front Panel LEDs: Front panel LEDs indicate which loading segment the digital LCD current display is reporting; Bank 1 current level is reported when the Bank 1 LED is on; Bank 2 current level is reported when the Bank 2 LED is on; Total output of both banks is reported when both LEDs are on
Certifications: Tested to UL 60950-1 (USA, Canada), Class A (Emissions), NOM (Mexico), RoHS compliant
Specifications: Output
Output Power Capacity: 10 kWatts / 10 kVA
Max Configurable Power: 10 kWatts / 10 kVA
Nominal Output Voltage: 208 V,208 V 3PH
Efficiency at Full Load: 92.00%
Output Voltage Distortion: Less than 5% at full load
Output Frequency (sync to mains): 57 - 63Hz for 60Hz nominal
Crest Factor: Unlimited
Waveform Type: Sine wave
Output Connections: (1) Hard Wire 5-wire (3PH + N + G)
Input
Nominal Input Voltage: 208 V,208 V 3PH
Input Frequency: 60Hz +/- 3Hz
Input Connections: Hard Wire 5-wire (3PH + N + G)
Input voltage range for main operations: 177 - 239 (208 V) V
Communications & Management
Interface Port(s): RJ-45 10 Base-T ethernet for web / SNMP / Telnet management, SmartSlot
Audible Alarm: Alarm when on battery / distinctive low battery alarm / configurable delays
Approvals: cUL Listed, FCC Part 15 Class A, ISO 140...
Features: Higher Availability
Provides utility power to attached equipment when switched to maintenance bypass mode.
Allows UPS maintenance or replacement of the UPS without discontinuing power to critical equipment.
Flexibility
Easily installed - the UPS and utility power are both connected to the MicroPOD with the supplied cords.
Allows scheduled UPS maintenance to ensure continuous uptime without having to shut down protected equipment.
Rotary switch with indicators make the unit simple to operate.
Plug-and-play connectability for both input and output.
Compatible with any brand of UPS system.
Lowest Total Cost Of Ownership
Assures system uptime during maintenance activities.
Extreme affordability.