Any questions? Our AI beta will help you find out quickly.
Try me now
Learn more about the CyberPower OL1KRM
Model
Brand
CyberPower
Series
Essential Online UPS
Model
OL1KRM
Input
International Version
120V
Input Voltage Range
100 - 125V
Input Frequency
40 - 70 Hz
Input Connection
NEMA 5-15P
Output
VA Rating
1000 VA
Watts
800 Watts
Output Voltage
100/110/115/120/125 VAC +/- 2% (configurable)
Outlets
8
Outlet Type
8 x NEMA 5-15R
Battery
Battery Type
Sealed Lead Acid
Battery Run Time
4 min Full Load / 11.5 min Half Load
Battery Recharge Time
4 Hours (0% to 90% charged)
Battery Replaceable
RB1270X2G
Details
Alarms
Battery Mode Low Battery Overload UPS Fault
Interface Port
USB, Serial
Approvals
UL 1778 CSA C22.2 NO.107.3 FCC Part 15 Class B
Rackmountable
Yes
Surge Protection
Surge Energy Rating
710 Joules
Protection
UPS Output Cut Off Immediately or Input Fuse Circuit Breaker Protection Overload Protection: Line Mode: 102% to 130% load for 12s - bypass Line Mode: 131% to 150% load for 2 s - bypass >150% load 300ms -no output Battery Mode: 102% to 130% load for 12 s - shutdown Battery Mode: >130% for 2 s -shutdown Bypass Mode: 102% to 110% warning Bypass Mode: 111% to 130% load for 5min - no output Bypass Mode: 131% to 150% 16s - no output >150% for 300ms - no output